Detail PCE-PA 8000
FEATURES :
- Analysis of a network of 3 phases/ 4 conductors 3 phases / 3 conductors, 1 phase /
2 conductors, 1 phase/ 3 conductors
- Measures effective real value of current and voltage Measures active, apparent and reactive
power
- Power Factor ( PF) , phase angle ( ¦ )
- Measures voltage up to 600V
- Measures current up to 1200 A
- It meets the IEC 1010 and CAT III 600V standards
- Integrated timer and calendar to record data
- Measured values are recorded in the SD card
- Data is stored in Excel format for further valoration
- Data can be transferred to a PC through data cable
- Large 3, 7 " LCD display
Technical Specifications
Voltage ( AC V)
Measurement range
Resolution
Accuracy
10 V ... 600 V ( phase to neutral)
0, 1 V
± ( 0, 5 % + 0, 5 V)
10 V ... 600 V ( phase o neutral)
Current ( AC A)
Measurement range
Resolution
Accuracy
20 A
0, 001 A ( < 10 A)
0, 01 A ( e10 A)
± ( 0, 5 % + 0, 1 V)
200 A
0, 01 A ( < 100 A)
0, 1 A ( e100 A)
± ( 0, 5 % + 0, 5 A)
1200 A
0, 1 A ( < 1000 A)
1 A ( e1000 A)
± ( 0, 5 A + 5 A)
Active power
Measurement range
Resolution
Accuracy
0 KW ... 9, 999 KW
0, 001 KW
± ( 1 % + 0, 008 KW)
10 KW ... 99, 99 KW
0, 01 KW
± ( 1 % + 0, 008 KW)
100 KW ... 999, 9 KW
0, 1 KW
± ( 1 % + 0, 8 KW)
1 MW ... 9, 999 MW
0, 001 MW
± ( 1 % + 0, 008 MW)
Apparent power
Measurement range
Resolution
Accuracy
0 KVA ... 9, 999 KVA
0, 001 KVA
± ( 1 % + 0, 008 KVA)
10 KVA ... 99, 99 KVA
0, 01 KVA
± ( 1 % + 0, 08 KVA)
100 KVA ... 999, 9 KVA
0, 1 KVA
± ( 1 % + 0, 8 KVA)
1 MVA ... 9, 999 MVA
0, 001 MVA
± ( 1 % + 0, 008 MVA)
Reactive power
Measurement range
Resolution
Accuracy
0 KVAR ... 9, 999 KVAR
0, 001 KVAR
± ( 1 % + 0, 008 KVAR)
10 KVAR ... 99, 99 KVAR
0, 01 KVAR
± ( 1 % + 0, 08 KVAR)
100 KVAR ... 999, 9 KVAR
0, 1 KVAR
± ( 1 % + 0, 8 KVAR)
1 MVAR ... 9, 999 MVAR
0, 001 MVAR
± ( 1 % + 0, 008 MVAR)
Active energy
Measurement range
Resolution
Accuracy
0 KWh ... 9, 999 KWh
0, 001 KWh
± ( 1 % + 0, 008 KWh)
10 KWh ... 99, 99 KWh
0, 01 KWh
± ( 1 % + 0, 08 KWh)
100 KWh ... 999, 9 KWh
0, 1 KWh
± ( 1 % + 0, 8 KWh)
1 MWh... 9, 999 MWh
0, 001 MWh
± ( 1 % + 0, 008 MWh)
Apparent energy
Measurement range
Resolution
Accuracy
0 KVAh ... 9, 999 KVAh
0, 001 KVAh
± ( 2 % + 0, 008 KVAh)
10 KVAh ... 99, 99 KVAh
0, 01 KVAh
± ( 2 % + 0, 08 KVAh)
100 KVAh ... 999, 9 KVAh
0, 1 KVAh
± ( 2 % + 0, 8 KVAh)
1 MVAh... 9, 999 MVAh
0, 001 MVAh
± ( 2 % + 0, 008 MVAh)
Reactive energy
Measurement range
Resolution
Accuracy
0 KVARh ... 9, 999 KVARh
0, 001 KVARh
± ( 2 % + 0, 008 KVARh)
10 KVARh ... 99, 99 KVARh
0, 01 KVARh
± ( 2 % + 0, 08 KVARh)
100 KVARh ... 999, 9 KVARh
0, 1 KVARh
± ( 2 % + 0, 8 KVARh)
1 MVARh... 9, 999 MVARh
0, 001 MVARh
± ( 2 % + 0, 008 MVARh)
Power factor
Measurement range
Resolution
Accuracy
0 ... 1
0, 01
± 0, 04
Phase angle
Measurement range
Resolution
Accuracy
-180º ... 180º
0, 1º
± 1º
Frequency
Measurement range
Resolution
Accuracy
45 Hz ... 65 Hz
0, 1 Hz
0, 1 Hz
General technical specifications
Display
3, 7 " LCD ( 320 x 240 pixels) with LED backlight
Electrical properties
AC V, AC A, active power, apparent power, power factor, phase angle, mains frequency
Voltage ranges
10 V ... 600 V AC, automatic range selection
Security / Standards
IEC1010CAT III 600V
AC V input resistance
10 M©
Operation frequency of current clamps
40 Hz ... 1 kHz
Tested operation frequency of current clamps
45 Hz ... 65 Hz
Overload protection
AC V
720 V rms
AC A
1300 A with current clips
Memory
SD card
Measurement rate
1 second
Data logger
SD
Measurement rate
2 seconds... 7200 seconds
Data output
USB or RS-232, depending
on the connection cable
Operating temperature
0 º C ... 50 º C
Operating humidity
< 80 % H.r.
Power
8 x 1, 5 V AA batteries / mains component
Input current
Meter: 300 mA DC
Clamp: 34 mA DC
Max. diameter
50 mm
Weight
Meter: 948 g ( with batteries)
Clip: 467 g ( with cable)
Dimensions
Meter: 225 x 125 x 64 mm
Clamp: 210 x 64 x 33 mm
jaw: 86 mm ( exterior)
Delivery contents:
1 x PCE-PA 8000 Power Analyzer
3 x current clamps
4 x test cables
4 x alligator clips
1 x 2 GB SD card
1 x 9 V DC mains component
8 x batteries 1, 5 V AA
1 x carrying case
Tampilkan Lebih Banyak